Z-ONE 6 ZONE VALVE CONTROL

Product #: CAL-ZVR106

Weight: 6.6

Description

Multi-zone valve relay and boiler operating control for multiple zone hydronic heating systems. Interfaces with low voltage thermostats or any other low voltage controllers having a switching action. Controls from 3 to 6 zones (model dependent). System circulator pump and secondary pump is turned on whenever any zone calls for heat. LED indicators provide functional status and easy system troubleshooting. ZVR series is a perfect match with Caleffi Z-oneā„¢ motorized zone valves. Power supply: 120 VAC 50/60 Hz Transformer voltage: 24 VAC Max transformer load: 40 VA (ZVR103 and ZVR104) 80 VA (ZVR106) Electrical switch rating: 20 A max combined Electrical switch rating pumps: 120 VAC, 5 A each Dry contact rating (AUX, XX, ZONE 1 E/S): 120 VAC, 2 A each Resettable fuse: automatic High capacity 40 VA transformer standard for 3 and 4 zone models (expandable to 80 VA) 80 VA transformer standard for 6 zone control model